CVE-2022-4608

CVE-2022-4608CVE-2022-4608

hitachienergy / rtu500_firmware

Description

A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.

Scoring

CVSS 7.5 ()
VectorCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Last modified2026-11-10
Sourced from NVD. Curated for EU compliance use cases by Adam Lundqvist, Founder at SQUR.